Security

C-Tec XFP Repeater Panels

C-Tec XFP Repeater Panels
  Zoom
Our Price:  £329.67
List Price:  £382.50
Saving Of:  £52.83 (14%)
(Exc. 20% VAT)(£395.60 Inc. VAT)
+
Variants:  
Control Type:  

Catalogue No:  XFP510-16
Brand:  C-Tec

Current Item:  

  

Click for delivery info

C-Tec

Brochure

Special Offer:  Free delivery is available when you order £250.00 or more of selected products.

C-Tec XFP Repeater Panels

C-TEC’s XFP range of networkable repeater panels offer high performance at a competitive price.

Now fully approved to EN54 parts 2 & 4 by the Loss Prevention Certification Board, the XFP repeater panels are available in three formats to match the main fire panel – 16 zone and 32 zone.

Repeater panels are supplied complete with networking capability to connect and communicate directly with C-Tec's XFP range of analogue addressable networkable fire panels, you will need to order either CFP761 (16 zone) or AFP711 (32 zone) network card expander as appropriate for the XFP main panel in order to connect repeater/s.

Recognised by governments and regulatory authorities across the world, the product's third-party approval demonstrates that all XFP variants have been extensively tested for functionality and performance, comply with EN54 Parts 2 and 4 and meet the overall standards of the Loss Prevention Certification Board, the leading international certification body in the fields of security and fire protection.

Up to eight XFP master panels (any variant) can be interconnected, making the range ideal for use in larger applications such as office blocks, shopping complexes and big industrial sites as well as in smaller, stand-alone applications due to its competitive price.

The XFP is also fully compatible with C-TEC’s new Hush Button fire alarm solution for Houses of Multiple Occupation.

XFP Range Features

  • Full compatibility with Apollo’s XP95/Discovery and Hochiki’s ESP protocols
  • The ability to interconnect up to eight XFP main panels (any variant) onto a two wire RS485 network. Alternatively, up to eight XFP repeaters can be connected to a non-networked XFP main panel
  • Two independently programmable conventional sounder circuits
  • Two programmable inputs
  • Fault output relay and three programmable relay outputs with voltage free changeover contacts
  • Three zone dependency functions (A, B & C to EN54-2 Clause 7.12)
  • Day/night (building occupied/unoccupied) function
  • Investigation delay period function
  • Individual sensitivity settings for each device
  • Phased evacuation and delays to outputs facility (to EN54-2 Clause 7.11)
  • Alarm counter that records the number of times the panel has been in an alarm state (to EN54-2 Clause 7.13)
  • Powerful short circuit protected loop drivers, capable of
  • supporting up to 40 loop powered 10mA sounders per loop
  • Integral EN54 switch mode PSU rated @ 185-260V a.c.50/60Hz (1.4A on 16 zone panel, 3A on 32 zone panel)
  • Earth fault monitoring
  • Push button access code or keyswitch entry to Access Levels 2 and 3 (depending on model purchased)
  • Easy to read, 80 character back-lit display
  • 40 characters of custom text per device
  • 999 event monitoring
  • Comprehensive test facilities (to EN54-2 Clause 10) and a wide range of maintenance & commissioning functions including auto-learn loops, monitor a point, test outputs, one man walk test and loop continuity test
  • Intuitive Windows based upload-download PC program that allows the system to be programmed quickly and easily
  • Full compatibility with C-TEC’s new Hush Button fire alarm solution for houses of multiple occupation